Description
Knauf Rigid Plenum Liner with ECOSE® Technology is a
heavy-density mat-faced fiber glass board insulation bonded with
ECOSE Technology. Its base board is brown with a black mat facing
to give the airstream a smooth, tough surface, that resists damage
during installation and operation.
ECOSE Technology
ECOSE Technology is a revolutionary new binder chemistry
that makes Knauf Insulation products even more sustainable than
ever. It is based on rapidly renewable bio-based materials rather
than non-renewable petroleum-based chemicals traditionally used in
fiber glass insulation products. ECOSE Technology reduces binder
embodied energy and does not contain phenol, formaldehyde, acrylics
or artificial colors.
Application
Knauf Rigid Plenum Liner with ECOSE Technology is specifically
designed as an interior insulation material for heating,
ventilating and air conditioning plenums and sheet metal ducts. It
offers an optimum combination of efficient sound absorption, low
thermal conductivity and minimal air surface friction.
Features
- Low thermal conductivity.
- Fire-resistant, non-corrosive.
- Tough and resilient.
- Certified for indoor air quality as a low emitting product by
The GREENGUARD Environmental Institute to both the GREENGUARD
Certification ProgramSM and the more stringent
GREENGUARD Children and SchoolsSM standard.
- Sustainability: Carbon negative: meaning Knauf insulation
products used for thermal insulating purposes recover the energy
that it took to make them in just hours or a few days, depending on
the application. Once installed, the product continues to save
energy and reduce carbon generation as long as it is in place.
- Fiber glass insulation with ECOSE Technology contains three
primary ingredients: sand, one of the world’s most abundant and
renewable resources; post-consumer recycled bottle glass; and ECOSE
Technology which reduces binder embodied energy by up to 70%.
-
Benefits
Energy conservation.
- Better temperature control.
- Lower operating costs.
- Greatly reduces noise from fans and mechanical equipment as
well as cross-talk and air movement.
- Withstands damage from normal handling and shop abuse.
- If necessary, can be cleaned in accordance with NAIMA’s
“Cleaning Fibrous Glass Insulated Air Duct Systems Recommended
Practices.”
Specification Compliance
In U.S.:
- ASTM C 1071; Type II
- ASTM G 21
- GREENGUARD Indoor Air Quality Certified®
- GREENGUARD Children and SchoolsSM
- California Title 24
- NFPA 90A and 90B
In Canada:
Technical Data
Surface Burning
Characteristics
- UL/ULC Classified.
- Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255 and UL
723.
Temperature Range (ASTM C
411)
- Up to 250°F (121°C). Max thick 3"
Air Velocity (ASTM C
1071)
- Maximum 5000 fpm (1524 mpm).
- Tested to 12,500 fpm (3810 mpm).
Corrosiveness (ASTM C
665)
- Does not accelerate corrosion on steel, copper or
aluminum.
Corrosion (ASTM C
1617)
- The corrosion rate in mils/yr will not exceed that of the 1 ppm
chloride solution.
Water Vapor Sorption (ASTM C
1104)
Microbial Growth (ASTM C 1338,
G 21)
- Does not promote or support the growth of mold, fungi or
bacteria.
Application and Specification
Guidelines
Storage
Inside storage is recommended. Protect
stored Rigid Plenum Liner from water damage or abuse. If stored
outside, stack cartons on pallets and cover adequately to prevent
moisture infiltration.
Fabrication and
Application
- Install Knauf Rigid Plenum Liner in metal duct and plenums
operating at 250°F (121°C) service temperature or less and
velocities of 5000 fpm (1524 mpm) or less.• Liner shall be applied
with the treated surface facing toward the air stream.
- Mechanical fasteners shall not compress the liner more than
1/8" (3.2 mm) and shall be installed perpendicular to the airstream
surface. All fasteners must meet “Standard for Mechanical
Fasteners-MF-1-1975.”
- Adhesives which conform to ASTM C 916 shall be applied to the
sheet metal with at least 90% coverage.
- All internal duct areas designated to be lined shall be
completely covered with liner. Transverse joints shall be firmly
butted together with no gaps, and coated with adhesive. All exposed
leading edges shall be coated with adhesive.
- Mechanical fasteners shall be used to secure the rigid plenum
liner and spaced in accordance with the chart and diagram to the
right.
- Corner joints shall be overlapped so no gaps are present. Top
pieces shall be supported by side pieces.
- All longitudinal joints shall be coated with adhesive
conforming to ASTM C 916 at velocities over 2500 fpm (762 mpm). All
damaged areas to the airstream surface shall be repaired with an
adhesive that conforms to ASTM C 916.
Fiber Glass and Mold
Fiber glass insulation will not
sustain mold growth. However, mold can grow on almost any material
when it becomes wet and contaminated. Carefully inspect any
insulation that has been exposed to water. If it shows any sign of
mold it must be discarded. If the material is wet but shows no
evidence of mold, it should be dried rapidly and thoroughly. If it
shows signs of facing degradation from wetting, it should be
replaced. Air handling insulation used in the air stream must be
discarded if exposed to water.
Notes
The chemical and physical properties of Knauf Rigid Plenum Liner
with ECOSE® Technology represent typical average values determined
in accordance with accepted test methods. The data is subject to
normal manufacturing and testing variations. The data is supplied
as a technical service and and is subject to change without notice.
References to numerical flame spread ratings are not intended to
reflect hazards presented by these or any other materials under
actual fire conditions.
Check with your Knauf Insulation sales
repersentative to assure information is current.
Knauf Rigid Plenum Liner with ECOSE
Technology products are certified for indoor air quality by The
GREENGUARD Environmental Institute™, to both the GREENGUARD
Certification ProgramSM and the more stringent GREENGUARD For
Children and Schools™ Standard. www. greenguard.org
The GREENGUARD INDOOR AIR QUALITY
CERTIFIED Mark is a registered certification mark used under
license through the GREENGUARD Environmental Institute.
SOUND ABSORPTION COEFFICIENTS,
1/3 OCTAVE BANDS (ASTM C 423, TYPE A
MOUNTING)
| Density |
Thickness |
125 Hz |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
NRC |
3.0 PCF
(48 kg/m3) |
1"
(25 mm) |
.13 |
.24 |
.56 |
.83 |
.92 |
.98 |
.65 |
3.0 PCF
(48 kg/m3) |
1.5"
(38 mm) |
.19 |
.41 |
.89 |
1.02 |
1.03 |
1.04 |
.85 |
3.0 PCF
(48 kg/m3) |
2"
(51 mm) |
.33 |
.67 |
1.07 |
1.07 |
1.03 |
1.06 |
.95 |
FRICTION LOSS (INCHES OF WATER PER 100
FT.)
Air
Velocity
(FPM) |
10"
HD |
16"
HD |
24"
HD |
32"
HD |
40"
HD |
72"
HD |
100"
HD |
| 500 |
.047 |
.026 |
.016 |
.011 |
.008 |
.004 |
.003 |
| 600 |
.066 |
.037 |
.022 |
.016 |
.012 |
.006 |
.004 |
| 700 |
.088 |
.049 |
.030 |
.021 |
.016 |
.008 |
.005 |
| 800 |
.113 |
.063 |
.038 |
.027 |
.020 |
.010 |
.007 |
| 900 |
.142 |
.079 |
.048 |
.034 |
.026 |
.013 |
.008 |
| 1000 |
.173 |
.096 |
.059 |
.041 |
.031 |
.015 |
.010 |
| 2000 |
.657 |
.366 |
.222 |
.157 |
.119 |
.059 |
.040 |
| 3000 |
1.449 |
.808 |
.491 |
.345 |
.263 |
.130 |
.087 |
| 4000 |
2.548 |
1.421 |
.863 |
.607 |
.463 |
.228 |
.154 |
| 5000 |
3.954 |
2.206 |
1.339 |
.943 |
.719 |
.354 |
.239 |
THERMAL CONDUCTANCE, C AND
RESISTANCE, R (ASTM C 177)
@ 75°F (24°C)
MEAN TEMPERATURE
| Density |
Thickness |
C-Value |
C-Value (SI) |
R-Value |
R-Value (SI) |
| 3.0 PCF (48 kg/m3) |
1" (25 mm) |
.23 |
1.31 |
4.3 |
.76 |
| 3.0 PCF (48 kg/m3) |
1.5" (38 mm) |
.15 |
.85 |
6.5 |
1.15 |
| 3.0 PCF (48 kg/m3) |
2" (51 mm) |
.11 |
.62 |
8.7 |
1.53 |
STANDARD SIZES
| Density |
Thickness |
Width |
Length |
| 3.0 PCF (48 kg/m3) |
1" (25 mm) |
24" (610 mm) |
48" (1219 mm) |
| 3.0 PCF (48 kg/m3) |
1.5" (38 mm) |
24" (610 mm) |
48" (1219 mm) |
| 3.0 PCF (48 kg/m3) |
2" (51 mm) |
24" (610 mm) |
48" (1219 mm) |
MADE-TO-ORDER
SIZES
| Density |
Thickness |
Width |
Length |
|
3.0 PCF
(48 kg/m3)
|
1"
(25 mm) |
24", 48"
(610 mm, 1219 mm) |
36", 72", 96", 120"
(914, 1829, 2438, 3048 mm) |
|
3.0 PCF
(48 kg/m3)
|
1.5"
(38 mm) |
24", 48"
(610 mm, 1219 mm) |
36", 72", 96", 120"
(914, 1829, 2438, 3048 mm) |
|
3.0 PCF
(48 kg/m3)
|
2"
(51 mm) |
24", 48"
(610 mm, 1219 mm) |
36", 72", 96", 120"
(914, 1829, 2438, 3048 mm) |